Electrical

Motors and starters — starting current, protection and what actually kills them

Why an induction motor draws six times its rated current on starting, what each starting method trades away, and why nearly every motor failure ends as overheated insulation.

IntermediateOil & GasPetrochemicalPharmaceutical

Standards referencedIEC 60034IEC 60079-14IEC 61800IEEE 841

Motors are where most of a plant’s electrical energy ends up. Nearly all of them are three-phase squirrel cage induction motors, for the same reason most piping is carbon steel: cheap, rugged, and with nothing much to go wrong.

How it turns

A three-phase supply into the stator produces a magnetic field that rotates at the synchronous speed:

Ns = 120 × f / poles

At 50 Hz: 3000 rpm for 2 poles, 1500 for 4, 1000 for 6. At 60 Hz: 3600, 1800, 1200.

The rotor always turns slightly slower than the field — typically 1 to 3% slower. That difference is slip, and it is not a defect: without it there would be no relative motion, no induced rotor current and no torque. A motor at exactly synchronous speed produces nothing.

Slip increases with load, which is why a heavily loaded motor runs marginally slower and draws more current.

The starting problem

At standstill an induction motor looks electrically like a short circuit. Started straight onto the supply it draws six to eight times its full load current for a few seconds.

On a small motor nobody notices. On a large one it drags the switchboard voltage down, and everything else on that board feels the sag — contactors drop out, drives trip, lighting dips.

Current against time for four starting methods. Direct on line spikes to around seven times full load current and holds there before dropping. Star-delta sits near two and a half times with a step at changeover. A soft starter ramps to about three times. A variable frequency drive stays close to full load current throughout.
The same motor, four ways of starting it. The height of that first spike is what the rest of the switchboard feels.
Motor starting methodsSource: General practice; starting current figures are multiples of full load current (FLC)
Direct on line (DOL)6 – 8 × FLCFullLowestSmall motors, and anything that must start against full load
Star–deltaAbout 2 – 3 × FLCAbout one thirdLowMotors that can run up unloaded — fans, unloaded compressors
AutotransformerSelectable by tapReduced in proportionModerateLarge motors on weak supplies where taps allow tuning
Soft starterAdjustable, typically 2 – 4 × FLCRamped smoothlyModeratePumps and conveyors, where a mechanical shock matters
Variable frequency drive (VFD)About 1 × FLCFull, from zero speedHighestWhere speed control is wanted anyway — then starting is free

An induction motor started straight onto the supply draws six to eight times its full load current. On a small motor nobody notices. On a large one it dips the voltage across the whole switchboard, and everything else connected to it feels the sag. Every method below exists to soften that moment.

A VFD sidesteps the whole problem: it starts the motor at low frequency and ramps up, so starting current is barely above running current and full torque is available from zero speed. It is the most expensive option, which is why it is usually chosen for the speed control and the easy starting comes free.

What kills motors

A row of motor control centre cubicles in an indoor switchroom, each door carrying a selector switch, indicator lamps and an isolator handle, with cable trunking running overhead.
A motor control centre. One cubicle per motor, and behind each door the contactor and protective device doing the two jobs neither could do alone.
What kills a motor, and what is watching for itSource: IEC 60034 and general protection practice
Sustained overloadCurrent above rating, windings slowly overheatThermal overload relay, set from the motor's FLCDeliberately slow to act, so a normal start does not trip it
Short circuitVery high current, immediate damageFuses or a magnetic trip in the breakerMust act in milliseconds — far faster than the overload relay
Earth faultCurrent leaking to the frame; a shock riskEarth fault relay, or core-balance CTSensitivity depends on how the system neutral is earthed
Single phasingTwo phases carry the whole load and overheat rapidlyPhase failure or negative sequence relayA plain overload relay may not see it until the damage is done
Blocked coolingMotor overheats at perfectly normal currentWinding thermistors or RTDs embedded in the statorCurrent-based protection is blind to this — the temperature is the clue
Frequent startingHeat builds up faster than it can be shedStart counter or thermal model in the protection relayMotor datasheets state permitted starts per hour, hot and cold
Bearing failureVibration, then rotor rubbing the statorVibration monitoring, bearing RTDsOn critical machines only; elsewhere it is found by routine checks
VFD bearing currentsPitting and fluting of the bearing racesNot detected — it is designed outInsulated bearings or a shaft earthing brush, and a properly bonded screen

Almost every motor failure ends the same way — the winding insulation gets too hot and breaks down. The protections below are all different ways of noticing that before it happens, and each catches a cause the others would miss.

Almost every failure ends the same way — winding insulation too hot for too long. Each protection above is a different way of noticing that, and each catches something the others cannot.

The pairing worth remembering:

  • An overload relay is deliberately slow, so a legitimate six-times start does not trip it. That means it is useless against a short circuit.
  • Fuses or a magnetic trip act in milliseconds against a short circuit. That means they are useless against a slow overload, which never reaches their threshold.

Neither replaces the other, which is why motor starters contain both.

Reading a motor nameplate

Beyond voltage, current and kW, four things matter:

Insulation class — the temperature the winding material can take. Class F (155 °C) is standard, often with a Class B (130 °C) temperature rise, giving a deliberate margin that extends life.

IP rating — dust and water ingress, as covered in hazardous areas. Outdoor plant motors are typically IP55 or better.

Duty type — S1 is continuous running, which covers most plant motors. S2 to S9 cover short-time and intermittent duties, where the motor relies on cooling down between runs.

Ex marking, if it is in a hazardous area. A motor is a large piece of electrical equipment with hot surfaces and internal sparking, so it carries the full certification — usually Ex d (flameproof) or Ex e (increased safety) in Zone 1, Ex n in Zone 2.

VFDs bring their own problems

A drive solves starting and gives speed control, but it introduces three things:

Harmonics. The drive draws non-sinusoidal current, which distorts the supply and heats transformers, cables and neutrals. Large installations need a harmonic study, and often filters.

Bearing currents. Fast switching induces a voltage on the shaft, which discharges through the bearing. Each discharge pits the race, and over months produces the characteristic fluting pattern. The fix is insulated bearings or a shaft earthing brush — plus the VFD cable screen bonded at both ends, the deliberate exception noted in cables.

Cooling at low speed. A motor with a shaft-mounted fan cools less as it slows, while still carrying current. Running a standard motor slowly for long periods overheats it. The answer is a separately driven cooling fan, or a motor rated for the duty.

What to take away

  • Synchronous speed is 120f/poles. Slip is what produces torque, not a fault.
  • DOL starting draws six to eight times full load current. Everything else trades torque to reduce that.
  • Starting method follows the load’s torque demand, not the motor rating.
  • Overload relays are slow by design; fuses are fast. Both are needed, neither replaces the other.
  • Current-based protection is blind to a cooling failure. Winding temperature sensors are not.
  • VFDs bring harmonics, bearing currents and low-speed cooling problems — and in a hazardous area, motor and drive must be certified together.

Check your understanding

10 questions. Nothing is recorded — this is just for you.

1A 4-pole induction motor runs on a 50 Hz supply. What is its synchronous speed?
2Why is star–delta starting unsuitable for a motor that must start against full load?
3A motor is running at normal current but its windings are overheating. Which protection sees this?
4Why do VFD-driven motors sometimes need insulated bearings or a shaft earthing brush?
5Why is slip necessary rather than a defect?
6Why does a motor starter contain both an overload relay and fuses or a magnetic trip?
7What does the S1 duty type on a motor nameplate mean?
8Why does running a standard motor slowly on a drive for long periods overheat it?
9A drive is fitted to an existing Ex d motor in a Zone 1 area to save energy. What is wrong?
10What are harmonics, in the context of a variable frequency drive?

#electrical#motors#protection#vfd