Variable speed drives — throttling with electricity instead of a valve

Why slowing a pump saves far more energy than closing a valve, what a VSD does to the motor it drives, the harmonics and bearing currents that arrive with it, and why the cable between drive and motor is not an ordinary cable.

IntermediateOil & GasPetrochemicalPharmaceuticalInfrastructure & BuildingsAutomotive

Standards referencedIEC 61800IEEE 519IEC 60034-25

Most process machinery runs at one speed because a motor connected to the mains has only one speed to offer. Flow is then adjusted by throttling a valve — which works, and wastes a great deal of energy doing it.

A variable speed drive changes the frequency the motor sees, so the machine can run at whatever speed the duty actually needs.

Why slowing down saves so much

For a centrifugal pump, fan or compressor, the relationships are steep:

  • Flow varies with speed
  • Head varies with the square of speed
  • Power varies with roughly the cube of speed

This applies to centrifugal machines. A positive displacement pump moves a fixed volume per revolution, so flow follows speed but power does not fall in the same way — the saving is real but far smaller, and the reason for fitting a drive there is usually control rather than energy.

What the drive actually does

It rectifies the incoming AC to DC, smooths it on a DC link, then switches that DC rapidly to synthesise an AC output at whatever frequency is wanted.

The switching is the source of both the usefulness and every complication that follows. It happens thousands of times a second with very fast voltage edges, and those edges do not stay politely inside the drive.

Cooling: the problem people meet first

Harmonics: what the drive does to everything else

A drive does not draw a smooth sinusoidal current. It draws it in pulses as the rectifier conducts, and mathematically that pulsed draw is equivalent to currents at multiples of the supply frequency — the harmonics.

They flow back into the network and cause trouble that appears nowhere near the drive:

  • Transformers and cables carry current that does no useful work but heats them
  • Neutral conductors can carry more than the phases in some arrangements
  • The voltage waveform distorts for everything else on the same board
  • Sensitive electronics and metering misbehave for no locally visible reason

The cable is not an ordinary cable

Bearing currents

This one surprises people because it is a mechanical failure with an electrical cause.

The drive’s switching leaves the motor shaft sitting at a voltage relative to earth. The oil film in the bearing is an insulator — until the voltage exceeds what it can withstand, at which point it discharges through the bearing.

Each discharge removes a little metal. Over months the raceway develops characteristic fluting, the bearing gets noisy, and it fails. Replacing it with an identical bearing produces the same failure again, because nothing about the cause has changed.

The remedies give the current an easier path than through the rolling elements: an insulated bearing at the non-drive end, a shaft earthing ring that conducts the charge away, or both on a large machine.

The open front of a large variable speed drive cabinet showing the power stack with finned heatsinks and cooling fans, a bank of DC link capacitors above, a three-phase line reactor at the base and heavy copper busbar running down one side.
The capacitors at the top are the DC link, the finned stacks are where the switching losses leave as heat, and the reactor at the bottom is there to civilise what the drive does to the supply. All of it is the price of varying the speed.

Regeneration: energy coming back

Slow a large fan or a loaded conveyor faster than it wants to stop, and the machine drives the motor. The motor becomes a generator and pushes energy back into the drive, raising the DC link voltage until the drive trips to protect itself.

Three answers, in increasing cost: decelerate more slowly, fit a braking resistor to burn the energy as heat, or fit a regenerative drive that returns it to the supply. On a machine that decelerates often, the third pays for itself.

Before retrofitting a drive to an existing motor

Also worth settling before the order: whether the motor is in a hazardous area, because a drive changes the thermal behaviour the Ex certification was based on and the combination must be certified together — see Ex installation and inspection.

What to take away

  • Power falls with roughly the cube of speed on centrifugal machines, which is why a drive beats a throttling valve so heavily.
  • Standard motors cool themselves with their own fan. Low speed means little air, and overheating below rated current.
  • Harmonics are caused locally and felt site-wide; they belong in the design, not the investigation.
  • The output cable must be screened, bonded at both ends, and kept away from instrument cabling.
  • Bearing currents are an electrical cause with a mechanical failure. Fitting another identical bearing fixes nothing.
  • Regeneration trips drives on overvoltage. Ramp slower, add a braking resistor, or regenerate.
  • Check inverter duty before retrofitting, and re-check the Ex certification if the motor is in a hazardous area.

Check your understanding

7 questions. Nothing is recorded — this is just for you.

1A centrifugal pump delivering 80 % of its flow is throttled by a control valve. What does a variable speed drive offer instead?
2Why can a motor overheat when run slowly on a drive, even below its rated current?
3What are harmonics, in the context of a drive?
4Why does the cable between a drive and its motor need to be screened?
5What causes bearing currents in a motor fed from a drive?
6A drive trips repeatedly on overvoltage while decelerating a large fan. Why?
7What should be checked before applying a drive to an existing motor?