Electrical

Cables — construction, selection and why sizing is never just about current

What the layers of a cable do, how power, control and instrument cables differ, the four things that decide a cable size, and why the published rating is never the rating you get.

BeginnerOil & GasPetrochemicalPharmaceutical

Standards referencedIEC 60502IEC 60364-5-52IEC 60079-14IEC 61892

Cables are where a great deal of a plant’s cost and nearly all of its installation labour sits. They are also where a design that looked fine on paper meets a hot cable tray in direct sun with forty other cables on it.

What the layers do

Cut through a typical armoured plant cable and you find, from the middle outward:

Cutaway section of a three-core armoured cable. Working outward from the centre: stranded copper conductors, coloured insulation around each core, filler between them, a bedding layer, a ring of steel armour wires, and an outer sheath.
Each layer has one job. The insulation sets the temperature limit, which is what sets the current rating.

Conductor — stranded copper, or aluminium in large sizes. Copper conducts better and terminates more reliably; aluminium is cheaper and lighter for a given capacity, but needs larger sizes and careful termination because it creeps under pressure and oxidises.

Insulation — keeps each core apart from its neighbours and from earth. This is the layer that sets the temperature rating, and therefore the current rating.

Bedding — a cushioning layer so the armour does not bite into the insulation.

Armour — steel wire (SWA) or aluminium wire (AWA) for mechanical protection. On LV cables the armour usually doubles as the earth path. Aluminium armour on single-core AC cables avoids the heating that steel would suffer from the magnetic field.

Outer sheath — the weatherproof, chemical-resistant skin, and the surface that carries the identification colour.

Insulation and sheath materialsSource: IEC 60502 and manufacturer data; conductor temperatures are the usual published values
PVCInsulation and sheath70160Cheap and tough, but emits dense toxic smoke and acid gas in a fire
XLPEInsulation90250Higher rating and better fault withstand than PVC. The plant default.
EPRInsulation90250More flexible than XLPE; favoured offshore and for trailing cables
LSZHSheath90250Low smoke, zero halogen — for enclosed and manned spaces
Silicone rubberInsulation180350High temperature duty; forms an insulating ash when burnt
Mineral (MICC)Insulation2501000Magnesium oxide in a copper sheath. Survives fire; needs sealed terminations.
PTFEInsulation200300Chemically inert, high temperature, expensive

The conductor temperature limit is what sets a cable's current rating. XLPE runs 20 °C hotter than PVC for the same size, which is why an XLPE cable of a given cross-section carries noticeably more current than the PVC equivalent.

The temperature column is the one doing the work. XLPE runs at 90 °C where PVC is limited to 70 °C, and that 20 °C is why an XLPE cable of a given size carries appreciably more current than the PVC equivalent.

Select for duty before size

Cable types by dutySource: IEC 60502, IEC 60092 and project cable schedules; construction codes vary by region
LV powerXLPE insulated, PVC bedded, steel wire armoured, PVC sheathedNo400/415 V supplies to motors, panels and heatersThe plant workhorse. Armour also serves as an earth path.
MV powerXLPE insulated, individually screened cores, armouredYes — per core3.3 kV to 33 kV distributionCore screens control the electric field; termination kits are specialised
VFD / motor driveXLPE, symmetrical cores, overall braid screen, armouredYes — overall braidInverter output to a motorThe screen must be bonded at both ends, unlike most instrument cable
ControlPVC or XLPE multicore, overall screen, armouredUsually overallSwitching signals, interlocks, status feedbackMulticore with spare cores allowed for — always specify spares
Instrument, analogueTwisted pair, individual and overall screens, armouredYes — pair and overall4–20 mA signals, RTD and thermocouple circuitsTwisting rejects magnetic pickup; the screen rejects electric pickup
Intrinsically safeAs instrument cable, with a light blue outer sheathYesIS circuits from a barrier to a field deviceBlue sheath is the identification convention — never use it for anything else
Fire resistantMineral insulated, or mica tape under XLPE, LSZH sheathedDepends on dutyEmergency shutdown, fire pumps, emergency lightingMust keep working during a fire, not merely resist spreading it
Thermocouple extensionMatched alloy conductors, twisted pair, screenedYesThermocouple signals back to the marshalling cabinetConductors must match the thermocouple type — copper introduces an error

A cable is selected for its duty first and its size second. Putting a power cable on an instrument duty is not merely wasteful — the screening, capacitance and segregation requirements are different, and a 4–20 mA signal run alongside a motor feeder will pick up interference.

The distinction that matters most is power versus signal.

A 4–20 mA instrument signal is a few milliamps travelling hundreds of metres. A motor feeder is hundreds of amps switching on and off. Run them together and the motor cable induces noise into the signal — so instrument cable is defended twice over:

  • Twisted pairs cancel magnetically induced interference, because the two conductors of a pair see opposing fields.
  • Screens intercept electrostatically coupled interference and conduct it to earth.

These are two different mechanisms addressing two different problems, which is why good instrument cable has both, and why it has individual screens per pair and an overall screen.

Four checks decide the size

Sizing a cable on load current alone is the classic beginner error. There are four checks and the largest answer wins.

1. Current carrying capacity

Start with the load, then apply the derating factors for the actual installation.

A heavily loaded galvanised ladder-type cable tray carrying armoured cables of several diameters in parallel rows, with a separate tray above carrying thinner instrument cables.
This is what a derating factor means physically. Every cable here is warming its neighbours, and the ones in the middle of the bunch cannot shed heat at all.
What reduces a cable's current ratingSource: Indicative factors only. IEC 60364-5-52 and the project's cable sizing standard give the values that govern.
High ambient temperature0.7 – 0.95Less temperature difference available to shed heatDesert and tropical sites bite hard here — 50 °C shade is not unusual
Grouping on a tray0.5 – 0.85Cables heat each other, and the ones in the middle cannot coolDepends on the number of cables and the spacing between them
Direct burial0.8 – 1.0Depends entirely on soil thermal resistivity and depthDry sandy soil is a far worse heat path than moist clay
Buried in ducts0.7 – 0.9The air gap in the duct insulates rather than conductsWorse than direct burial, and often overlooked
Direct solar radiation0.85 – 0.95Sun on the sheath adds heat the cable must also shedApplies to exposed outdoor runs; a sunshade recovers most of it
Enclosed in conduit or trunking0.7 – 0.9Trapped air, no convectionFill ratio matters as much as the enclosure itself
Harmonic content (VFDs, rectifiers)0.7 – 0.9Triplen harmonics add current in the neutral that the sizing ignoredThe neutral can carry more than the phases on a harmonic-rich load

A published current rating assumes one cable, in free air, at a stated ambient. A real plant cable is bunched with others on a hot tray in the sun — and the factors multiply together. Three factors of 0.8 leave you with barely half the rating you started from.

2. Voltage drop

Volts are lost along the length of the cable. A motor at the far end of a long run may see meaningfully less than nominal voltage, and a motor starting on low voltage draws more current, gets hotter and may not start at all under load.

Typical limits are around 3% for lighting and 5% for power, measured at full load. On long runs — a remote wellhead, a distant pump house — voltage drop, not current, usually decides the size.

3. Short circuit withstand

During a fault the cable carries enormous current until the protection clears it. The conductor must survive that heating without the insulation being destroyed.

This check couples cable sizing to the protection settings, which is why cable schedules and protection studies have to agree. A faster breaker allows a smaller cable; a slow one demands a larger one.

4. Earth fault loop impedance

The protective device must see enough fault current to operate within its required time. Too high an impedance in the earth path and the breaker takes too long — leaving a fault live and metalwork dangerous.

Installation is where designs are lost

Segregation. Power, control and instrument cables are separated on trays, by distance or by an earthed barrier. Crossing at right angles rather than running parallel minimises coupling.

Bending radius. Every cable has a minimum bending radius, typically 6 to 12 times its outside diameter. Pulling a cable round a tighter bend damages the insulation invisibly, and it fails later.

Pulling tension. There is a limit, and exceeding it stretches conductors and displaces insulation. Long pulls need rollers, lubricant and planning.

Glanding. The gland makes the mechanical seal, maintains the ingress rating and — on armoured cable — terminates the armour as an earth. In a hazardous area the gland is part of the certification, as covered in hazardous areas.

Close up of gloved hands terminating an armoured cable into a brass gland fitted to a cast metal junction box on a structural steel column outdoors. The cable outer sheath has been cut back and the steel wire armour splayed out into an even cone around the inner sheath, ready to be trapped between the gland cone and clamping ring. Coloured inner cores are visible passing through into the box, with process pipework blurred behind.
The armour fanned evenly all the way round, not bunched to one side. Those wires are the cable's earth path and its mechanical anchor, and they only become either once they are clamped in the gland — an armour that was trimmed off or left loose gives a termination that looks finished and is neither earthed nor retained.

Fire performance: two different things

These get confused constantly, and they are not the same.

Flame retardant — the cable resists spreading fire along its length. It stops being a fuse leading fire from one area to another. Most plant cable is flame retardant.

Fire resistant — the cable keeps working while burning, for a defined period. This is required only for circuits that must survive a fire: emergency shutdown, fire pumps, emergency lighting, escape systems.

LSZH is a third and separate property: low smoke, zero halogen. Ordinary PVC produces dense black smoke and hydrogen chloride when it burns, which blinds and injures people trying to escape and corrodes equipment. LSZH is specified in enclosed and manned spaces — accommodation, control rooms, tunnels — where the smoke matters more than the flame.

What to take away

  • Layers have jobs: insulation sets the temperature and therefore the rating, armour protects and often earths, the sheath keeps the weather out.
  • Select for duty first. Power, control and instrument cables are different products, not different sizes of the same one.
  • Twisting defeats magnetic pickup, screening defeats electrostatic pickup. Instrument cable needs both.
  • Earth instrument screens at one end. Earth VFD screens at both. The reason differs.
  • Four sizing checks — capacity, voltage drop, fault withstand, earth loop impedance — and the biggest answer wins.
  • Derating factors multiply, and can halve a published rating.
  • Flame retardant, fire resistant and LSZH are three different requirements.

Check your understanding

10 questions. Nothing is recorded — this is just for you.

1A cable is sized purely on the load current and nothing else. What is most likely to be wrong?
2Why are instrument cable cores twisted in pairs?
3A light blue outer sheath on a field cable means
4An instrument cable screen is normally earthed at one end only. Why?
5Why must a VFD cable screen be bonded at both ends, against the usual rule?
6Three derating factors of 0.8 apply to a cable — ambient, grouping and installation method. What is the combined effect?
7On a long run to a remote pump house, which sizing check usually governs?
8Why does the short circuit withstand check couple cable sizing to the protection settings?
9What is the difference between a flame retardant and a fire resistant cable?
10Why is LSZH cable specified in control rooms and accommodation?

#electrical#cables#installation#design