Electrical

Earthing and bonding — several different jobs sharing one word

Why a plant has more than one earth, the difference between earthing and bonding, how the neutral earthing decision shapes the whole system, and why static bonding has almost nothing to do with fault current.

IntermediateOil & GasPetrochemicalPharmaceutical

Standards referencedIEC 60364IEC 62305IEC 60079-14IEEE 142IEC 60079-32

“Earth” is one word doing at least six different jobs, and treating them as interchangeable is the source of a remarkable number of plant problems — from nuisance signal noise to fatalities.

Earthing and bonding are not the same

Earthing connects metalwork to the general mass of earth, giving current somewhere to go.

Bonding joins metal parts to each other so they sit at the same potential, whether or not they are connected to earth at all.

The distinction matters because of what each is trying to prevent. Earthing is about giving fault current a route so the protection operates. Bonding is about ensuring there is no voltage difference between two things a person might touch simultaneously, or between two metal objects close enough for a spark to jump.

A static bonding cable carries almost no current. It is not undersized — it is doing a different job.

The several earths

The different earths on a plant, and what each is forSource: IEC 60364, IEC 62305, IEC 60079-14; resistance targets are indicative and project-specific
System (power) earthGive fault current a path back to the source so protection operatesTransformer and generator neutralsBelow 1 Ω at substationsWithout it a fault may not draw enough current to trip anything
Protective (equipment) earthKeep exposed metalwork at safe potential during a faultMotor frames, panels, cable armour, structuresContinuity matters more than absolute valueThis is the one that stops a fault making a handrail lethal
Instrument earthGive signals a clean, noise-free referenceCable screens, instrument reference railsBelow 1 Ω, and kept cleanJoined to the main earth at ONE point only, in the marshalling area
Intrinsically safe earthGive IS barriers a guaranteed low-impedance referenceZener barrier earth railsBelow 1 ΩIts integrity is part of the IS certification, not just good practice
Static bondingEqualise potential so no spark can jump between metal partsTanks, road tankers, drum filling points, flangesBelow 10 Ω — a low bar, deliberatelyIt is about equalising, not about conducting fault current
Lightning protection earthTake a strike to ground without it finding another routeAir terminals, down conductors, tall structures, stacksBelow 10 ΩNeeds low INDUCTANCE as well as low resistance — short, straight runs
Cathodic protectionDeliberately hold buried steel at a protective potentialBuried pipelines, tank bottomsNot an earth at all — an applied potentialMust be isolated from the earth grid or the protection is drained away

People say 'earth' as though there is one. There are several, they do different jobs, and some of them must not be joined to each other except at one defined point. Mixing an instrument earth into the power earth is a classic cause of unexplained signal noise.

Why a fault needs an earth at all

Take a motor with a winding fault to its frame. Without an effective earth path the frame sits at some voltage above true earth — and it stays there, live and looking entirely normal, until somebody touches it.

With a good earth path, fault current flows, and it flows in enough quantity that the protective device sees it and disconnects the supply in a fraction of a second.

So the requirement is not simply “connect it to earth”. It is low enough impedance in the whole loop that the protection actually operates in the required time. An earth connection too poor to trip the breaker is worse than useless, because it looks like protection and is not.

Touch and step potential

When large fault current enters the ground, the earth’s surface around that point does not stay at one potential — it slopes away.

  • Touch potential — the difference between a structure a person is holding and the ground they stand on.
  • Step potential — the difference between their two feet, a pace apart.
A faulted structure discharging current into the soil. A curve above the ground line shows the ground potential peaking at the fault and falling away with distance. One figure touches the structure, spanning the difference between hand and feet; another stands a pace away, spanning the difference between two feet.
Fault current entering the soil tilts the ground potential. Neither hazard requires touching anything live.

Both can be lethal near a substation earth during a fault. The defences are a buried mesh grid that flattens the gradient, and a layer of crushed rock at the surface to raise the resistance in series with a person.

The neutral earthing decision

How the source neutral is earthed shapes the entire electrical system.

How the system neutral is earthed, and what that buys youSource: IEEE 142 (the Green Book) and general distribution practice
Solidly earthedVery high — similar to a short circuitProtection trips immediatelyLV systems, 400/415 V distributionLarge fault energy means arc flash risk and equipment damage
Low resistance earthedLimited, typically 100 – 1000 ATrips, but with far less damage at the faultMV distribution, 3.3 kV to 33 kVNeeds earth fault protection sensitive enough to see the reduced current
High resistance earthedVery limited, typically under 25 AAlarms rather than trips — the plant keeps runningCritical continuous processes where a trip is itself a hazardA second fault on another phase becomes a phase-to-phase short
Reactance earthedLimited by a reactorTrips, with fault current tuned to the systemGenerator neutralsChosen to match generator damage curves
Unearthed (isolated / IT)Only small capacitive currentNo trip — an insulation monitor alarmsOffshore, marine, some critical control suppliesThe first fault must be found and cleared before a second one arrives

This one decision shapes the whole electrical system. It sets how much current an earth fault draws, whether the plant trips instantly or keeps running, and how much damage the fault does before anyone notices. There is a genuine trade-off here between continuity of supply and fault damage.

This is a genuine trade-off, not a right answer:

  • Solidly earthed gives a big fault current that trips protection decisively — and does real damage at the fault, with significant arc flash energy.
  • High resistance earthed limits fault current so much that a single earth fault merely alarms, and the process keeps running. That is invaluable where a trip is itself hazardous — but the first fault must be found and fixed, because a second fault on another phase turns into a phase-to-phase short.

Static: the hazard with no fault

In a hydrocarbon or powder plant, static electricity is a major ignition source, and none of it involves a fault.

Charge is generated by separation — liquid flowing through a pipe, powder sliding down a chute, a belt running over a pulley. If charge accumulates on something insulated, the potential rises until it discharges as a spark. If that happens where flammable vapour is present, the result is an ignition.

Controls, in order of importance:

  1. Bond everything together. Tanker to gantry, drum to filling nozzle, flange to flange across a non-conducting gasket.
  2. Limit filling velocity, especially at the start of filling a tank when splashing generates most charge.
  3. Fill from the bottom, or use a dip pipe, so the liquid does not splash and spray.
  4. Allow relaxation time before dipping or sampling, so accumulated charge can drain.
  5. Control people and clothing — antistatic footwear and clothing in powder handling areas, because a charged person is an effective spark source.

Lightning: low inductance, not just low resistance

Lightning protection is a separate discipline under IEC 62305, but one point is worth carrying over.

A lightning strike is a very fast event, and for fast events inductance matters more than resistance. A down conductor with a neat right-angle bend or a coiled spare length presents high impedance to a strike, and the current will look for a better route — possibly through something you did not intend.

Down conductors are therefore run short, straight and direct, with generous bend radii. A beautifully dressed installation with tidy 90° corners is, here, a worse installation.

Practical failures

Paint under a bonding connection. Paint is an insulator. The mating surfaces of an earth or bond connection must be cleaned to bright metal and then protected afterwards. This is probably the most common earthing defect on site.

Copper to aluminium directly. A galvanic couple that corrodes and loses continuity over a few years. Bimetallic washers or transition joints exist for this.

Earth continuity assumed through mechanical joints. A bolted flange, a threaded conduit or a hinged panel door is a mechanical joint, not a guaranteed electrical one. Where continuity matters, a dedicated bonding conductor is fitted.

Cable armour used as the sole earth where it is not permitted. Acceptable in many LV installations, but not everywhere — and in hazardous areas the gland and armour termination are part of the certification, as in hazardous areas.

Earth grid never tested after backfill. The grid is buried early and covered. Test it before it disappears, because excavating to find a poor joint later costs many times what the test would have.

Testing

An earthing inspection pit with its cover lifted aside, showing a copper earth electrode joined to bare stranded copper conductor by a bolted clamp, in damp soil.
The pit exists so this joint can be seen and tested for the life of the plant. Buried and unrecorded, a bad connection here is found only by digging.

Fall of potential — the classical measurement of an earth electrode’s resistance, using two temporary spikes at distance. Needs space and is done at commissioning.

Clamp-on testing — measures a loop without disconnecting anything. Convenient for routine checks on a meshed system.

Continuity testing — proves bonding conductors are actually connected, which is what matters for most protective and static bonding.

Earth fault loop impedance — proves the protection will actually operate in time. This is the test that answers the question earthing exists to answer.

What to take away

  • Earthing gives current a path to earth; bonding equalises potential between metal parts. Different jobs.
  • A plant has several earths. Instrument and IS earths join the main earth at one point only.
  • An earth connection too poor to operate the protection is not protection.
  • Neutral earthing is a trade-off: solid earthing trips decisively and does damage; high resistance earthing alarms and keeps running, but the fault must still be found.
  • Static needs bonding, velocity control and relaxation time — and a non-conducting section silently breaks the bond.
  • For lightning, inductance matters: short, straight, generous bends.
  • Paint under a bonding connection is a defect.

Check your understanding

10 questions. Nothing is recorded — this is just for you.

1What is the difference between earthing and bonding?
2Why is an instrument earth joined to the main plant earth at only one point?
3A high resistance earthed MV system develops a single earth fault. What happens?
4A road tanker is bonded before loading flammable liquid. What is that preventing?
5An earth connection exists but its impedance is too high for the breaker to operate in time. How should that be regarded?
6What is step potential?
7A high resistance earthed system raises an earth fault alarm. The plant is running normally. What should happen?
8Why do lightning down conductors avoid right-angle bends and coiled spare length?
9A plastic spool piece is fitted in a metal pipeline handling flammable liquid. What has it created?
10Which test answers the question that earthing exists to answer?

#electrical#earthing#safety#static#lightning