Electrical

Power quality and harmonics — the drive that damages four things it is not connected to

Where harmonic current actually goes, why a transformer runs hot at half load, the neutral that carries more than the phases, shaft voltage and bearing fluting, and why instrument noise that follows drive speed is an electrical problem.

IntermediateOil & GasPetrochemicalPharmaceuticalInfrastructure & BuildingsAutomotive

Standards referencedIEC 60364IEC 60255IEEE 43CEA Regulations

Power quality is the subject where the fault and the damage are usually in different rooms, owned by different people, and charged to different disciplines. A variable speed drive installed to save energy on a pump can cook a transformer, overheat a neutral conductor, inject noise into instrument loops and destroy motor bearings, and not one of those four will be investigated as an electrical supply problem.

A power quality analyser hung inside an open drive cubicle with its display showing a distorted current waveform, three flexible current clamps looped around the incoming cores and voltage leads made off to the terminals, with the drive heatsink and a capacitor bank visible behind.
Half an hour of measurement at the board settles arguments that otherwise run for years between the electrical, rotating equipment and instrument teams.

What a harmonic is, in the only terms that matter here

A sine wave at fifty hertz is what the supply is meant to be. Any load that draws current in a non-sinusoidal way — a rectifier, a drive, a switched-mode power supply, an LED driver, a UPS — draws current that can be described as the fundamental plus components at multiples of it. Those components are the harmonics.

Two consequences follow, and they are different from each other.

Harmonic current flows back through the supply to the source, heating cables, transformers and neutrals along the way.

Harmonic voltage distortion appears because that current flows through the source impedance. The distorted voltage sits on the common bus, and every other load connected there receives it. This is the mechanism by which one badly behaved load affects equipment it has no connection to.

A drive-fed motor at the centre with four routes drawn out from it: harmonic current flowing upstream into the transformer and distorting the bus voltage, triplen harmonics adding in the neutral conductor, common mode current flowing to earth through motor cable capacitance and returning through instrument cable screens, and shaft voltage discharging through the motor bearings. A panel lists how each victim looks when it is failing and which discipline is usually blamed for it.
The drive is connected to one of these. It damages all four.

The upstream damage

Transformers suffer most. Eddy current loss rises roughly with the square of frequency, so a current component at the eleventh harmonic heats the windings out of all proportion to its size. A transformer feeding a drive-heavy board can run at its thermal limit while its ammeter reads half load, which is why such transformers are specified k-rated or deliberately de-rated.

Neutral conductors are the quiet one. In a balanced three-phase system the fundamental currents cancel in the neutral, which is why neutrals were historically sized smaller than phases. The third harmonic and its odd multiples — the triplens — arrive in phase with each other and add instead. On a board full of single-phase electronic loads the neutral can carry more current than any phase, in a conductor of half the cross section, with no protective device watching it.

Capacitors for power factor correction are a resonance risk rather than a heating one. Their impedance falls with frequency while the supply inductance rises, and at some order the two resonate. The result is a capacitor bank drawing a harmonic current many times what anyone intended, which is why capacitors fail on drive-heavy plants and why a detuning reactor is fitted.

The downstream damage, which is the part that gets misdiagnosed

The inverter side of a drive is a different problem from the harmonics on its supply side. It is not about the fifty hertz waveform at all — it is about how fast the output transistors switch.

Common mode current. Each switching edge has a steep rise, and the motor cable has capacitance to earth. The edge drives a current pulse into that capacitance, and that current has to get back to the drive. If the cable screen is terminated properly at both ends with a full circumferential gland, it returns along the screen where it belongs. If it is terminated with a pigtail, or at one end only, it returns through the earth system and through anything else conductive on the way — including instrument cable screens.

That is why instrument noise which follows drive speed is a drive installation problem rather than a transmitter problem, and why the first thing to look at is the gland, not the loop.

Shaft voltage and bearing currents. The same fast edges impress a voltage on the motor shaft. When it exceeds the breakdown strength of the thin lubricant film in the bearing, it discharges through it, and each discharge removes a little metal from the race. Early on the surface looks frosted. Later it develops the regular washboard pattern called fluting, which then drives the vibration that finally gets the machine condemned.

The measures against shaft current form a hierarchy. Correct symmetrical screened motor cable with circumferential glands and a short low-impedance earth path reduces the current at source. An insulated bearing at the non-drive end blocks one path. A shaft earthing brush offers a preferred path. The last two manage the current; only the first reduces it.

Voltage dips, which are the other half of power quality

Harmonics are the steady state problem. The transient one is the dip, and on an Indian industrial supply it is a weekly event rather than an annual one.

A dip of a couple of hundred milliseconds is enough to drop out a contactor, stop a drive on undervoltage and reset an unprotected control system, and the plant then spends a shift restarting from an event that lasted a fraction of a second. The defences are specific rather than general: ride-through settings on the drives, contactors with a hold-in arrangement or DC-fed coils, and a UPS that actually holds up the control system — see battery and DC system integrity.

What makes dips an integrity subject rather than a nuisance is that nobody records them. The event appears in the operations log as an unexplained trip, and after the fifth one somebody starts looking at the process.

What a power quality survey should produce

  1. Voltage and current distortion at the main bus and at each significant feeder, over at least a full production cycle including start-up and shutdown.
  2. The individual orders, not just the total figure, because mitigation is chosen against specific orders.
  3. Neutral current on every four-wire board, measured rather than inferred.
  4. A record of dips and interruptions over the monitoring period, with duration and depth.
  5. A statement of what changes, with the measurement repeated afterwards.

That last item is what separates a survey from a report. A plant that measured, mitigated and measured again knows what it bought.

Where this goes next

Check your understanding

7 questions. Nothing is recorded — this is just for you.

1A distribution transformer feeding a drive-heavy board runs hot while its measured load current sits at half of rating. What is the most likely explanation?
2Why can the neutral conductor of a three-phase four-wire system carry more current than any phase?
3Instrument signals on a plant become noisy and the noise follows the speed of a nearby variable speed drive. Where should the investigation start?
4What causes the fluting pattern sometimes found on a failed motor bearing race on a drive-fed machine?
5Which measure addresses shaft voltage at its source rather than diverting the damage?
6What does total harmonic distortion measured at a bus tell you that the same measurement on a single feeder does not?
7A plant plans to add a large new drive. What is the most useful thing to do before the order is placed?

#electrical#harmonics#power-quality#vsd#motors#bearings#transformers#emc