Why does 4–20 mA start at 4 and not 0?

NAMUR NE 43

The obvious design would run 0 to 20 mA, with 0% of the range at 0 mA. It was tried, and it is a bad idea for a reason that becomes obvious the first time a cable is damaged.

Zero has to be distinguishable from nothing

With a 0–20 mA signal, a tank that is genuinely empty and a cable that has been cut by an excavator both produce 0 mA. The control system cannot tell them apart. The operator sees “empty” and has no reason to doubt it.

With 4–20 mA, an empty tank reads 4 mA and a cut cable reads 0 mA. The two are different, and the system can be made to say so. That offset is called a live zero, and it is the whole reason the standard begins where it does.

This generalises. Any signal scheme where the bottom of the range coincides with the failure state is a scheme that cannot report its own failure.

The 4 mA has a second job

In a two-wire transmitter — the usual arrangement — the same pair of wires carries the power in and the signal out. There is no separate supply. The transmitter draws its operating current from the loop and regulates that draw to represent the measurement.

Which means its entire electronics must run on less than 4 mA, because 4 mA is the smallest current it will ever be allowed to draw. At 24 V that is about 90 mW for the sensor, the amplifier, the compensation, the display and whatever digital communication it supports.

That constraint is why two-wire field instruments were historically simple, and why the move to HART and to richer field electronics was a genuine engineering achievement rather than a matter of adding features.

The band outside 4–20 is used too

A fault does not have to be a clean 0 mA to be detectable, and the convention for this is NAMUR NE 43:

Current Meaning
≤ 3.6 mA Fault — signal low
3.8 to 4.0 mA Live zero band, still valid
4 to 20 mA The measurement
20.0 to 20.5 mA Over-range, still valid
≥ 21 mA Fault — signal high

So the measuring range is really 3.8 to 20.5 mA, and the regions beyond are reserved for the instrument to report that it has a problem. A transmitter that has failed its own self-test can drive its output deliberately to 3.6 or to 21.5 mA and say so without ambiguity.

Which direction it drives on failure is a configurable choice, and it is a safety decision rather than a preference: an instrument whose high reading would trip a process should usually fail high, so that failure and trip point in the same direction. That logic belongs with the safety instrumented system design, not with the instrument technician.

Why 20 at the top

Low enough that the energy in the loop can be limited for intrinsic safety — which is what makes 4–20 mA workable in a Zone 0 area at all — and high enough to sit well above the electrical noise picked up by a long cable in a plant full of motors and drives.

It is also convenient: a 250 Ω resistor turns 4–20 mA into 1–5 V, which is why that value appears so often in loop drawings and why a technician with a multimeter can read a loop either way.

More on how the signal is produced and what sits at each end in what is a transmitter, and on proving the whole path end to end in installation and loop checking.